90 VAV-PRC011M-EN
DDC Controls
•CO
2
demand controlled ventilation enables a HVAC system to adjust ventilation flow based on
the current CO
2
concentration in the zone. Trane demand controlled ventilation strategies are
pre-defined for simplified application and can be easily customized to meet the needs of a
specific system.
Trane DDC VAV Controller Logic with VV550 Controls
Control Logic
Direct Digital Control (DDC) controllers are today’s industry standard. DDC controllers share
system-level data to optimize system performance (including changing ventilation requirements,
system static pressures, supply air temperatures, etc.). Variables available via a simple twisted-
shielded wire pair include occupied/unoccupied status, minimum and maximum airflow setpoints,
zone temperature and temperature setpoints, air valve position, airflow cfm, fan status (on or off),
fan operation mode (parallel or series), reheat status (on or off), VAV unit type, air valve size,
temperature correction offsets, flow correction values, ventilation fraction, etc.
With the advent of LonMark open protocol, the most reliable VAV controller is now available for
ANY system. Gone are the days of being locked into a single supplier. Trane DDC controllers
provide Trane-designed solid-state electronics intended specifically for VAV applications including:
4. Space Temperature Control
5. Ventilation Flow Control (100% outside air applications)
6. Flow Tracking Space Pressurization Control (New feature)
Note: Flow sensor DP (in. wg) is measured at the flow ring to aid in system balancing and commissioning. See “Valve/Controller
Airflow Guidelines” in each section for unit performance.
Space Temperature Control
Space temperature control applications are where Trane emerged as an industry leader in quality
and reliability. This did not occur overnight and has continued to improve as our controller and
control logic has improved over time. STC employs controller logic designed to modulate the
supply airstream and associated reheat (either local or remote) to exactly match the load
requirements of the space.
Additionally, minimum and maximum airflow and specific controller sequence requirements are
pre-programmed to ensure that appropriate ventilation standards are consistently maintained.
When connected to a Trane Tracer SC control system, trend logging, remote alarming, etc. are
available to fully utilize the power and capabilities of your systems.
Figure 4. Flow sensor single vs. airflow delivery
0.01
0.1
1
5
10 100 1,000 10,000
Cfm
Flow Sensor DP (In. wg)
4"
12"
10"
8"6"
5"
14"
16"