Trane Round In/Round Out Detailliste Seite 88

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 158
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 87
88 VAV-PRC011M-EN
DDC Controls
Trane LonMark™ DDC VAV Controller (VV550)
This LonMark™ certified controller uses the Space Comfort Controller (SCC) profile to exchange
information over a LonTalk™ network. Networks with LonMark certified controllers provide the
latest open protocol technology. Being LonMark certified guarantees that owners and end-users
have the capability of adding Trane products to other “open” systems and relieves owners of the
pressure and expense of being locked into a single DDC supplier. The Trane VV550 VAV controller
with VariTrane VAV units can be applied to more than just Trane systems. When a customer buys
a Trane VAV unit with Trane DDC controller, they take advantage of:
Factory-commissioned quality
Knowing they have selected the most reliable VAV controllers in the industry
Trane as a single source to solve any VAV equipment, or system-related issues
The most educated and thorough factory service technicians in the controls industry
Over 150 local parts centers throughout North America that can provide what you need, when
you need it.
Don’t let your existing controls supplier lock you out of the most recognized name in VAV system
control in the industry. Specify Trane open-protocol systems.
The features of this controller are explained below.
General Features and Benefits
Assured Accuracy
Proportional-plus-integral control loop algorithm for determining required airflow needed to
control room temperature. Airflow is limited by active minimum and maximum airflow
setpoints.
Pressure-independent (PI) operation that automatically adjusts valve position to maintain
required airflow. In certain low-flow situations or in cases where the flow measurement has
failed, the DDC controller will operate in a pressure-dependent (PD) mode of operation.
When combined with the patented Trane Flow ring and pressure transducer, flow is repeatable
to +/- 5% accuracy across the Pressure Independent (PI) flow range. (See Valve/Controller
Airflow Guidelines section).
Improved 2-Point Air Balancing is available – Assures optimized flow-sensing accuracy across
the operating range. This provides a more accurate airflow balancing method when compared
to typical single-point flow correction air balancing.
Analog input resolution of +/- 1/8°F within the comfort range maximizes zone temperature
control yielding excellent comfort control.
Reliable Operation
Built for life – Trane products are designed to stand the test of time, with a proven design life
that exceeds 20 years.
Fully factory tested – fully screened and configured at the factory. All features are tested
including fan and reheat stage energization, air valve modulation, and controller inputs and
outputs.
Safe Operation
All components, including the controller, pressure transducer, transformer, etc. are mounted
in a NEMA 1 sheet metal enclosure and are tested as an assembly to UL1995 standards. The
result is a rugged and safe VAV, controller, and thus, overall unit.
When in PI-mode, EH is disabled when the sensed flow is below the minimum required.