82 VAV-PRC011M-EN
DDC Controls
Note: Flow sensor DP (in. wg) is measured at the flow ring to aid in system balancing and commissioning. See “Valve/Controller
Airflow Guidelines” in each section for unit performance.
Space Temperature Control
Space temperature control applications are where Trane emerged as an industry leader in quality
and reliability. This did not occur overnight and has continued to improve as our controller and
control logic has improved over time. STC employs controller logic designed to modulate the
supply airstream and associated reheat (either local or remote) to exactly match the load
requirements of the space.
Additionally, minimum and maximum airflow and specific controller sequence requirements are
pre-programmed to ensure that appropriate ventilation standards are consistently maintained.
When connected to a Trane Tracer™ SC control system, trend logging, remote alarming, etc. are
available to fully utilize the power and capabilities of your systems.
General Operation-Cooling
In cooling control action, the DDC controller matches primary airflow to cooling load. The DDC
controller will automatically change over to heating control action if the supply air temperature is
above a configured/editable setpoint. When the supply air temperature is less than 10 degrees
below this setpoint, the controller will automatically switch to cooling control action. The DDC
controller first chooses the Tracer SC -provided supply air temperature value to use for auto
changeover. If this is not available, it uses the temperature provided by the optional auxiliary
temperature sensor (must be installed for inlet temperature monitoring). If this is also not available,
it uses the heating/cooling mode assigned by Tracer SC or the DDC controllers service tool.
General Operation-Heating and Reheat
In heating control action, the DDC controller matches primary airflow to heating load. The DDC
controller will automatically change over to heating control action if the supply air temperature is
above a configured/editable setpoint. When the supply air temperature is less than 10 degrees
below this setpoint, the controller will automatically switch to cooling control action. The DDC
controller first chooses the Tracer SC-provided supply air temperature value to use for auto
changeover. If this is not available, it uses the temperature provided by the optional auxiliary
temperature sensor (must be installed for inlet temperature monitoring). If this is also not available,
it uses the heating/cooling mode assigned by Tracer SC or the DDC controllers service tool.
When heat is added to the primary air, the air is considered reheated. Reheat can be either local
(integral to the VAV unit in the form of an electric coil or hot water coil) or remote (typically existing
Figure 2. Flow sensor single vs. airflow delivery
0.01
0.1
1
5
10 100 1,000 10,000
Cfm
Flow Sensor DP (In. wg)
4"
12"
10"
8"6"
5"
14"
16"