VAV-PRC011M-EN 141
Application Considerations
Fan-Pressure Optimization
With Trane's Integrated Comfort System, the information from VAV terminal units can be used for
other energy-saving strategies. Fan-pressure optimization is the concept of reducing the supply fan
energy usage based on the position of the terminal unit dampers.
The control system allows this scenario. The system polls the VAV units for the damper position
on each unit. The supply fan is modulated until the most wide-open damper is between 85% and
95% open. The correct airflow is still being sent to the zones since the controls of the VAV units are
pressure-independent, and the fan modulates to an optimal speed and duct static pressure which
results in fan energy savings.
Ventilation Reset
The Ventilation Reset control strategy enables a building ventilation system to bring in an
appropriate amount of outdoor air per ASHRAE Standard 62.1. The basis for the strategy is
measuring airflow at each zone, calculating current system ventilation efficiency using the
multiple-zone system equations of the standard, and communicating a new outdoor airflow
setpoint to the air handler.
This strategy continually monitors the zone ventilation needs and system outdoor air intake flow,
minimizing the amount of ventilation air and increasing the energy efficiency of the system. This
ensures that the right amount of air is brought in at all times and that proper ventilation can be
documented. Trane has integrated this control ability into the VAV controls, air-handler controls,
and building controls.
For more detailed information on these energy-saving strategies, please refer to Additional VAV
System and Product References,” p. 156 for appropriate material.
Figure 11. Optimized static-pressure control
static
pressure
sensor
P
supply
fan
RTU controller
Tracer SC
VAV boxes with
DDC controllers
VFD
Seitenansicht 140