102 VAV-PRC011M-EN
DDC Controls
Dimensions
Specifications
Operating Temperature
-40 to 158ºF (-40 to 70ºC)
Storage temperature
-40 to 185ºF (-40 to 85°C)
Storage and operating humidity range
5% to 95% relative humidity (RH), non-condensing
Voltage
24 Vac/Vdc nominal ± 10%. If using 24 Vac, polarity must be maintained.
Receiver power consumption
<2.5 VA
Housing material
Polycarbonate/ABS (suitable for plenum mounting), UV protected, UL 94: 5 VA flammability rating
Mounting
3.2 in (83 mm) with 2 supplied mounting screws
Range
Open range: 2,500 ft (762 m) with packet error rate of 2%
Indoor: Typical range is 200 ft (61 mm); actual range is dependent on the environment. See BAS-
SVX55 for more detail.
Note: Range values are estimated transmission distances for satisfactory operation. Actual
distance is job specific and must be determined during site evaluation. Placement of WCI
is critical to proper system operation. In most general office space installations, distance is
not the limiting factor for proper signal quality. Signal quality is effected by walls, barriers,
and general clutter. For more information is available at http://www.trane.com.
Output power
North America: 100 mW
2.896 in (73.55 mm)
0.118 in
(3.00 mm)
4.677 in (118.8 mm)
3.385 in (86.0 mm)
2.480 in (63.0 mm)
R0.71 in
(R1.80 mm) TYP
0.236 in
(6.0 mm)
1.344 in (34.14 mm)
1.419 in (36.03 mm)
0.650 in (16.50 mm)
2.62 in (66.55 mm)
Kommentare zu diesen Handbüchern