150 VAV-PRC011M-EN
Application Considerations
Insulation
Matte-Faced
This type of insulation is used for typical applications. It consists of a fiberglass core covered by
a high-density skin. The dual-density construction provides good sound attenuation and thermal
performance.
Foil-Faced
This type of insulation is used in applications where there is some concern regarding airborne
contaminants entering the space, or dirt being trapped in the fibers of the insulation. The insulation
is composed of a fiberglass core laminated to a foil sheet. Foil-faced insulation will provide the
same sound attenuation performance as matte-faced insulation.
Double-Wall
This type of insulation is used in applications where there is extreme concern regarding airborne
contaminants entering the space or dirt being trapped in the fibers of the insulation. The insulation
is the same as the matte-faced insulation. However, after the insulation is installed, a second solid
wall of 26-gage steel covers the insulation. All wire penetrations of this insulation are covered by
a grommet. This type of insulation will result in higher discharge and radiated sound power.
Closed-Cell
This type of insulation is used in applications where IAQ and fibers are of primary concern. The
acoustics of the closed-cell insulation are similar to double-wall insulation. The thermal properties
are similar to fiberglass insulation. This insulation contains no fiberglass.
Acoustics
Acoustical Best Practices
Acoustics with terminal units is sometimes more confusing than it needs to be. As we know, lower
velocities within a unit leads to improved acoustical performance. Additionally, if the VAV terminal
unit has a fan, a lower RPM provides better Acoustical performance. It is as simple as that—there
are some catches, however.
Additional considerations will be discussed in more detail throughout this portion of Application
Considerations, such as unit size and type, appurtenance affects (due to insulation, attenuation,
etc.), certification, and computer modeling. Let’s take a look at the first consideration, sizing of
units.
Sizing of Units
Before blindly increasing the size of units, we must first understand what is setting the acoustics
within the space. In general, over 95% of acoustics in VAV terminal units, which set the sound
Encapsulated edges
Insulation in a VAV terminal unit is used to avoid condensation
on the outside of the unit, to reduce the heat transfer from the
cold primary air entering the unit, and to reduce the unit noise.
The VariTrane line offers four types of unit insulation. The type
of facing classifies the types of insulation. To enhance IAQ
effectiveness, edges of all insulation types have metal
encapsulated edges.