VAV-PRC011M-EN 125
Pneumatic Controls
Signal Limiter
Specifications
Factory Setting
Maximum output = 8 psig (55.2 kPa) Adjustable from 2–12 psig (13.8–82.7 kPa)
Main Air Pressure
Nominal 20 psig (138 kPa) 22 psig
(152 kPa) maximum acceptable pressure
Air Consumption
10 scim (0.164 L/m) at 20 psig (138 kPa) main air pressure
Operating Environment
50 to 120ºF (10 to 48.89°C)
Physical Dimensions
Width:. 1.1" (27.94 mm)|
Length: 0.9" (22.86 mm)
Height: 0.9" (22.86 mm)
Tubing Connections
9/100" (2.3 mm) nipples
Tubing Connections:
3/16" (4.8 mm) nipples for 1/4" (6.4 mm) polyethylene tubing
The pneumatic signal limiter is a pressure limiting type device. The output
pressure from the signal limiter is not allowed to rise above the signal
limiter’s setting. Adjustments to the output pressure setting are made via a
screw on the back side of the valve.