VAV-PRC011M-EN 11 7
DDC Controls
Humidity
5% to 95% RH, Non-Condensing
Ambient Temperature
-22 to 122°F (-30C to 50°C)
Storage Environment
-40 to 176°F (-40 to 80°C)
To r q u e
Min 35 in.-lb (4Nm), Independent of load
Running Time
95 sec. for 0 to 35 in-lb
Noise Rating
Less than 35 dB (A)
Weight
1.2 lbs (0.55 kg)
Static Pressure Controller
Specifications
Supply Voltage
24 VAC, 60 HZ
Maximum VA Load
No more than 12 VA
Recommended Wire Size
14 – 22 AWG Stranded
Housing Material
ABS
Components
Control box
Pressure sensor
Interconnecting wire
Static pressure tap
Fits standard 2" deep x 4" x 2 1/8" utility box.
The Trane static pressure controller will sense duct static pressure and
modulate a relief device in an effort to limit maximum duct static pressure.
An analog signal from the air probe is used to compare the difference in the
duct static pressure and the duct static pressure setpoint. The relief device
can be a VariTrane terminal or any blade damper device with the
specifications stated below. See VAV-EB-64 for installation and calibration.