VAV-PRC011M-EN 31
Single-Duct VAV Terminal Units
Hot Water Reheat Coil Notes (I-P)
1. Fouling Factor = 0.00025
2. Capacity based on 55°F entering air temperature and 180°F entering water temperature. Refer
to correction factors found in
Tab le 15, p. 31 and Ta bl e 16, p. 31 for different entering
conditions.
3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water
Temperature Difference (WTD).
4. For premium coils (.020” wall), side pressure drop increasesx 17% and water velocity increases
7% for fixed GPM.
Table 15. Temperature correction factors for water pressure drop (ft)
Average Water Temperature
Correction Factor
200
0.970
190
0.985
180
1.000
170
1.020
160
1.030
150
1.050
140
1.080
130
1.100
120
1.130
110
1.150
Table 16. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air
Correction Factor
40
0.32
50
0.40
60
0.48
70
0.56
80
0.64
100
0.80
125
1.00
140
1.12
150
1.20
160
1.28
180
1.44
200
1.60
Table 17. Coil only-water weights
Inlet
Size
1-Row Coil 2-Row Coil 3-Row Coil 4-Row Coil
Internal
Volume
Operating
Weight
Internal
Volume
Operating
Weight
Internal
Volume
Operating
Weight
Internal
Volume
Operating
Weight
(in
3
) (gal) (lbs) (in
3
) (gal) (lbs) (in
3
) (gal) (lbs) (in
3
) (gal) (lbs)
04 9.37 0.041 5.3 23.68 0.102 6.9 33.52 0.145 23 43.08 0.186 24
05 9.37 0.041 5.3 23.68 0.102 6.9 33.52 0.145 23 43.08 0.186 24
06 9.37 0.041 5.3 23.68 0.102 6.9 33.52 0.145 23 43.08 0.186 24
08 12.78 0.055 5.5 35.47 0.154 9.0 48.89 0.212 24 61.92 0.268 26
10 19.06 0.083 7.7 48.83 0.211 11.7 68.84 0.298 32 88.28 0.382 36
12 30.05 0.130 10.7 67.34 0.292 15.5 98.89 0.428 41 129.54 0.561 45
14 51.21 0.222 13.9 94.27 0.408 19.8 148.04 0.641 51 200.27 0.867 55
16 58.62 0.254 16.2 109.09 0.472 23.3 170.64 0.739 56 230.43 0.998 61
24x16 66.03 0.286 20.4 123.91 0.536 29.8 193.24 0.837 76 260.59 1.128 82
LAT EAT
MBH 921.7×
Cfm
--------------------------------------
+=
WTD EWT LWT
2MBH×
Gpm
------------------------
=–=