80 VAV-PRC011M-EN
DDC Controls
When combined with the patented Trane Flow ring and pressure transducer, flow is repeatable
to +/- 5% accuracy across the Pressure Independent (PI) flow range. (See Valve/Controller
Airflow Guidelines section).
Improved 2-Point Air Balancing is available – Assures optimized flow-sensing accuracy across
the operating range. This provides a more accurate airflow balancing method when compared
to typical single-point flow correction air balancing.
Analog input resolution of +/- 1/8°F within the comfort range maximizes zone temperature
control yielding excellent comfort control.
Reliable Operation
Built for life – Trane products are designed to stand the test of time, with a proven design life
that exceeds 20 years.
Fully factory tested – fully screened and configured at the factory. All features are tested
including fan and reheat stage energization, air valve modulation, and controller inputs and
outputs.
Safe Operation
All components, including the controller, pressure transducer, transformer, etc. are mounted
in a NEMA 1 sheet metal enclosure and are tested as an assembly to UL1995 standards. The
result is a rugged and safe VAV, controller, and thus, overall unit.
When in PI-mode, EH is disabled when the sensed flow is below the minimum required.
HW coil VAV units in ventilation flow control (VFC) have a Freeze protection algorithm to protect
the water coil and the internal space from water damage. This is accomplished by driving the
water valve to maximum position on alarm conditions.
System-Level Optimization
Trane controllers are designed to integrate into Trane Tracer™ Building Automation Systems and
leverage clear and clean unit-controller related data for system level control decisions. Integrating
a Trane VV550 controller into a Tracer SC Control System provides the next step in building system
control.
Specifically, system-level decisions on how to operate all components can be made. Energy
efficient optimization strategies like Static Pressure Optimization, Ventilation Reset, and CO
2
Demand-controlled Ventilation can be employed with the simple press of a button. The end-result
is the most efficient and reliable building control system available.
Simplified Installation
Factory Commissioned Quality – All Trane DDC VAV controllers are factory-commissioned. This
means that the DDC boards are powered and run-tested with your specific sequence parameters.
They are connected to a communication link to make sure that information and diagnostic data
function properly. Before any VariTrane™ VAV unit ships they must pass a rigorous quality control
procedure. You can be assured that a Trane VAV unit with Trane DDC VAV controls will work right
out of the crate.
Zone sensor air balance
– When applied to a Trane zone sensor with thumb-wheel and on/cancel
buttons, a balancing contractor can drive the primary air valve to maximum or minimum airflow
from the sensor to determine the point of calibration to be used (maximum will result in optimum
performance). The flow reading can then be calibrated from the sensor, without the use of
additional service tools. (Non-LCD versions)
Tenant-Finish Heat Mode
– In some office projects, the building is being constructed as tenants are
being identified. Tenant-finish heat mode is designed for applications when a given floor has not
been occupied. The main AHU system is used for heat and because the internal furnishings are not
complete, the sensors have not been installed. In this case, the primary valve drives open using