30 CAH-SVX01B-EN
Installation - Mechanical
TCP Base-to-Interior Wall Section Assembly
Note: Failure to completely compress the gasketing may result in air leakage.
1. Join the two units and secure with field provided 5/8-inch flat washers and 5/8-inch X 2-1/2-inch
grade 9 bolts though each of the six holes.
2. Apply caulk the length of the base between the 2-inch X 2-inch angle on the one base section
and the wall on the adjoining section. See Figure 17 below. Note: Use a polyurethane or
equivalent caulk.
3. Secure the 2-inch X 2-inch angle to the adjoining wall with #14 sheet-metal crews on 12-inch
centers along the length of the angle and wall.
Figure 17. TCP base-to-interior wall sections
Interior
wall
4-in. x 1/4-in. gasket
Secure 2-in. x 2-in. angle to wall
with #14 SM screws at 12-in. centers
Caulk
Split
Split
Interior
wall
Caulk
Caulk
Split
Split
Base-to-Wall Assembly Complete