
Maintenance
26 CXRC-SVX01F-EN
addition, use a quality detergent; like SPREX AC, OAKITE
161 or OAKITE 166 and COILOX.
Note: If detergent is strongly alkaline (i.e. has a pH value
greater that 8.5) after mixing, an aluminum
corrosion inhibitor must be added.
Coil Cleaning Procedure
1. Disconnect power to the unit.
2. Remove enough panels and components from the unit
to gain access to the coil.
3. Use a soft brush to remove loose dirt and debris form
both sides of the coil.
4. Straighten coil fins with fin comb as required.
5. Mix the detergent with water according to the
manufacturers instructions.
Observe all recommendations of the cleanser
manufacturer.The coil cleanser manufacturer’s
recommendations, warnings and cautions will at all times
take precedence to these instructions.
6. Place solution in the sprayer. Be sure to follow these
guidelines if using a high-pressure sprayer:
a. Minimum nozzle spray angle is 15°.
b. Spray solution at 90° to the coil face.
c. Keep sprayer nozzle at least six inches form the coil.
d. Sprayer pressure must not exceed 600 psi.
7. Spray leaving air side of the coil first then spray the
entering air side of the coil. Allow the detergent and
water solution to stand on the coil for five minutes.
8. Rinse both sides of the coil with cool, clean water.
9. Inspect the coil. If it still appears dirty, repeat the
cleaning procedure.
10. Reinstall all unit components and panels, and restore
electrical power to the unit.
Low Ambient Damper Adjustment
Intellipak DDC Controlled Units
Inspect damper blade for proper alignment and operation.
Dampers should be fully closed when positioning signal
from controller is 2 volts DC and should be fully open when
positioning signal from controller is 10 volts DC.To adjust
position remove VDC signal from actuator and check
dampers to ensure full closure. Check the 90% position
open by applying a 9-volt battery to the positioning signal.
Dampers should stroke 90% open when 9 VDC is applied
to the positioning signal inputs.
Thermostat Controlled Units
The same procedure can be used to inspect the operation
of the low ambient dampers on the thermostat-controlled
unit.The difference is that the positioning signal on the
thermostat-controlled unit will come from the control
panel in the CCRC/CIRC unit not from the Intellipak
controller. Inspect the operation of the pressure switches.
The switches should be open when sensing pressures less
that 170 psig and should be closed when sensing
pressures greater than 265 psig.
Troubleshooting
If operational difficulties are encountered, perform these
preliminary checks before calling a service technician.
• Check the system thermostat to ensure that all
setpoints are set correctly and that thermostat is
getting control power.
• Verify that the unit is receiving electrical supply power
and that all fuses are intact.
• Check the condenser for proper air flow and take
temperature readings across the condensing coils.
After completing the preliminary checks above, inspect the
unit for other obvious problems such as broken or
disconnected wires clogged grills or coils. If everything
appears to be in proper working order and the unit fails to
operate properly, contact a qualified service technician.
WARNING
Hazardous Pressures!
Coils contain refrigerant under pressure.When cleaning
coils, maintain coil cleaning solution temperature
under 150°F to avoid excessive pressure in the coil.
Failure to follow these safety precautions could result
in coil bursting, which could result in death or serious
injury.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
Kommentare zu diesen Handbüchern