
Maintenance
CXRC-SVX01F-EN 23
discharge line access port). Add refrigerant to reach
pressure of 12 to 15 psig.
4. Disconnect refrigerant cylinder. Connect dry nitrogen
cylinder to high side charging port and increase
pressure to 150 psig. Do not exceed high side
(discharge) unit nameplate design pressure. Do not
subject low side (suction) components to high side
pressure.
5. Check all piping joints, valves, etc. for leaks.
Recommend using electronic detector capable of
measuring 0.1 oz/year leak rate.
6. If a leak is located, use proper procedures to remove
the refrigerant/nitrogen mixture, break connections
and make repairs. Retest for leaks.
Make sure all service valves are open.
System Repair
1. If system is water cooled with service valves, or air
cooled, high and low side may be tested independently
by closing liquid line angle valve and water cooled unit
discharge line ball valve. Otherwise leave all valves
open and DO NOT exceed low side design pressure.
2. Connect R-410A refrigerant cylinder to charging port,
add refrigerant to reach pressure of 12 to 15 psig.
3. Disconnect refrigerant cylinder. Connect dry nitrogen
cylinder to high side charging port and increase
pressure to 150 psig. DO NOT exceed unit nameplate
design pressures. If testing complete system, low side
design pressure is maximum.
4. Check piping and/or components as appropriate for
leaks.
5. Recommend using electronic detector capable of
measuring 0.1 oz/year leak rate.
6. If a leak is located, use proper procedures to remove
the refrigerant/nitrogen mixture, break connections
and make repairs. Retest for leaks.
Make sure all service valves are open.
System Evacuation Procedures
Each refrigeration circuit must be evacuated before the
unit can be charged and started.
Use a rotary type vacuum pump capable of pulling a
vacuum of 100 microns or less.
Verify that the unit disconnect switch and the system
control circuit switches are “OFF”.
Oil in the vacuum pump should be changed each time the
pump is used with high quality vacuum pump oil. Before
using any oil, check the oil container for discoloration
which usually indicates moisture in the oil and/or water
droplets. Moisture in the oil adds to what must be removed
from the system, increasing pump down time.
When connecting the vacuum pump to a refrigeration
system, it is important to manifold the vacuum pump to
both the high and low side of the system (liquid line access
valve and suction line access valve). Follow the pump
manufacturer’s directions for the proper methods of using
the vacuum pump.
The lines used to connect the pump to the system should
be copper and of the largest diameter that can practically
be used. Using larger line sizes with minimum flow
resistance can significantly reduce evacuation time.
Important: Rubber or synthetic hoses are not
recommended for system evacuation
because they have moisture absorbing
characteristics which result in excessi ve
rates of evaporation, causing pressure rise
during the standing vacuum test.This
makes it impossible to determine if the
system has a leak, excessive residual
moisture, or a continual or high rate of
pressure increase due to the hoses.
An electronic micron vacuum gauge should be installed in
the common line ahead of the vacuum pump shutoff valve,
as shown in Figure 18, p. 24. Close Valves B and C, and
open Valve A.
Start the vacuum pump, after several minutes, the gauge
reading will indicate the maximum vacuum the pump is
capable of pulling. Rotary pumps should produce
vacuums of 100 microns or less.
OpenValves B and C. Evacuate the system to a pressure of
300 microns or less. As the vacuum is being pulled on the
system, there could be a time when it would appear that no
further vacuum is being obtained, yet, the pressure is high.
It is recommended that during the evacuation process, the
vacuum be “Broken”, to facilitate the evacuation process.
To break the vacuum:
Shutoff valves A, B, & C and connect a refrigerant cylinder
to the charging port on the manifold. Purge the air from the
hose. Raise the standing vacuum pressure in the system to
“zero” (0 psig) gauge pressure. Repeat this process two or
three times during evacuation.
Note: It is unlawful to release refrigerant into the
atmosphere. When service procedures require
working with refrigerants, the service technician
must comply with all Federal, State, and local laws.
Standing Vacuum Test
Once 300 microns or less is obtained, close Valve A and
leave valves B and C open.This will allow the vacuum
gauge to read the actual system pressure. Let the system
equalize for approximately 15 minutes.This is referred to
as a “standing vacuum test” where, time versus pressure
NOTICE:
Motor Winding Damage!
Do not use a megohm meter or apply voltage to a
compressor motor winding while it is under a vacuum.
Voltage sparkover could cause damage to the motor
windings.
Kommentare zu diesen Handbüchern