Installation - Mechanical
16 CXRC-SVX01F-EN
Refrigerant Piping Recommendation
Isolate refrigerant lines from the building to prevent
transferring line vibration to the structure. Do not secure
lines rigidly to the structure at any point, as this will defeat
the unit isolation system.
Interconnecting Piping
Refrigerant piping must be properly sized and applied.
These two factors have significant effect on both system
performance and reliability.
Important: Cleanliness is extremely important during
system installation to minimize residual
contaminants, such as oxidization and
scale. See Brazing procedure in
Maintenance section.
See Table 6, p. 16 for recommended discharge and liquid
line sizes.Table also includes unit connections sizes.
Verify compressor oil levels are near top of sight glass or
above.
Verify remote condenser system is sealed by momentarily
depressing liquid line access port valve. If holding charge
is present, continue piping installation. If not, locate and
repair any leaks. See section “Refrigerant LeakTest
Procedure,” p. 22 and “System Evacuation Procedures,”
p. 23 in Maintenance.
Work on only one circuit at a time to minimize system
exposure to moisture in the air.
Capped discharge and liquid line connections are located
near bottom of the indoor unit, left side for SCRF/SIRF, right
side for SCRG/SIRG. CCRC/CIRC connections are located
in the unit front, at top.
Remove cap with a tube cutter to minimize risk of getting
chips inside piping.
Figure 17. Typical configuration for constant drain oil
trap, which can be used in place of a double-
riser system.
Table 6. Refrigerant connection and piping sizes, in.
Connection Size
Circuit 1 Circuit 2
CXRC Size Liquid Discharge Liquid Discharge
20, 29, 32 5/8 7/8 5/8 7/8
35, 40, 50 7/8 1 3/8 5/8 7/8
60 7/8 1 3/8 5/8 7/8
Circuit 1 Circuit 2
SXRF Size Liquid Discharge Liquid Discharge
20, 25, 29 5/8 7/8 5/8 7/8
30, 35, 40, 50 7/8 1 3/8 5/8 7/8
60 7/8 1 3/8 5/8 7/8
Circuit 1 Circuit 2
SXRG Size Liquid Discharge Liquid Discharge
20, 25, 32 5/8 7/8 5/8 7/8
Interconnecting Tube
SXRF/CXRC
Size
Circuit 1 Circuit 2
Liquid Discharge Liquid Discharge
20/20 5/8 7/8 5/8 7/8
25/29 5/8 1 1/8 5/8 7/8
29/29 5/8 1 1/8 5/8 7/8
30/35 7/8 1 1/8 5/8 7/8
35/35 7/8 1 1/8 5/8 7/8
40/40 7/8 1 3/8
(a)
(a) Use 1 1/8” for vertical risers.
5/8 7/8
50/50 7/8 1 3/8 5/8 1 1/8
60/60 7/8 1 3/8 7/8 1 3/8
Circuit 1 Circuit 2
SXRG/CXRC
Size Liquid Discharge Liquid Discharge
20/20 5/8 7/8 5/8 7/8
25/29 5/8 1 1/8 5/8 7/8
32/32 5/8 1 1/8 5/8 1 1/8