Installation
VAV-SVN09B-EN 23
3. Field wire actuator 24VAC control voltage toVRRF DDC
controller. See Control Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
Analog and DDC Units:
Single Duct Electric Heat
1. Remove Power and Lock and Tag out unit if it hasn't
been done already.
2. Disconnect control wiring from heat relay(s) and field
wire cable(s) from kit by connecting heat relay coil(s) to
VRRF DDC controller binary output connections using
cable. See
Figure 16, p. 28 and Control Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
Analog and DDC Units:
Single Duct Hot Water
Note: Original hot water valve actuator may be
compatible with newVRRF DDC controller. If this is
true, skip the next two steps.
1. Isolate hot water valve and remove valve from system,
if necessary.
2. Install Proportional orTwo-Position hot water valve.
Ensure that the piping is correct to the new style valve.
3. Field wire actuator 24VAC control wiring to VRRF DDC
controller. See Control Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
Analog and DDC Fan Powered:
Fan control
1. Remove Power and Lock and Tag out unit if it hasn't
been done already.
2. Disconnect control wiring from fan relay(s) and field
wire cable(s) from kit by connecting fan relay coil(s) to
VRRF DDC controller binary output connections using
cable. See
Figure 13, p. 24, Figure 14, p. 26 and Control
Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
Note: Some Analog units used a duct pressure switch to
enable/disable fan. See below for change out to
retrofit using VRRF DDC controller.
Analog Fan-Powered:
Duct Pressure Switch only Fan Control
1. Remove Power and Lock and Tag out unit if it hasn't
been done already.
2. Disconnect duct pressure switch for fan Control in fan
control enclosure and replace it with relay from kit.
3. Connect line voltage wires to relay Normally Open
contacts using existing wires that were connected to
duct pressure switch, if possible.
4. Control voltage will be field wired from relay coil to
VRRF DDC controller binary output connections using
cable. See
Figure 15, p. 27 and Control Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.