Installation
VAV-SVN09B-EN 13
Analog Inputs
AI1
Space temperature; thermistor: 10k @77°F (25°C)
Range: 32°F to 122°F (0°C to 50°C)
AI2
Space setpoint; potentiometer: 1k
Range: from 50°F to 90°F (10°C to 32.2°C), */**
(thumbwheel) functionality supported
AI3
Spare
AI4
Discharge air temperature: 10k @77°F (25°C)
Range: from -40°F to 212°F (-40°C to 100°C)
AI5
Supply air temperature: 10k @77°F (25°C)
Range: from -40°F to 212°F (-40°C to 100°C)
Universal Inputs
UI1;
Spare, but recommended for relative humidity
Resistive/thermistor inputs: 0-10 Vdc inputs or 4-20
mA inputs
Current Mode Impedance: 200 , Voltage Mode
Impedance: 10k minimum
UI2;
Provided point for CO
2
Resistive/thermistor inputs: 0-10 Vdc inputs or 4-20
mA inputs
Current Mode Impedance: 200 , Voltage Mode
Impedance: 10k minimum
Pressure Inputs
•P1
Supply airflow, pressure transducer
From 0 to 2 in. water column (0 to 498 Pa)
•P2
Spare (recommended for dual duct secondary
airflow)
Binary Inputs
BI1
Occupancy
BI2
Spare
BI3
Spare
Binary Outputs
Analog Outputs
•AO1
Spare output.
Voltage output is 0 to 10 Vdc, 500 minimum
impedance.
Current output is 4-20 mA, 500 max. impedance.
Also can output 100 Hz PWM signal for control of a
Trane fan-powered ECM fan setpoint signal to the
EC motor.
•AO2
Spare.
Voltage output is 0 to 10 Vdc, 500 minimum
impedance.
Current output is 4-20 mA, 500 maximum
impedance.
Also used onTrane VAV units for SCR electric heat
0-to-10 Vdc modulation control.
Note: For more information on wiring spare points, refer
to theTracer UC400 Programmable Controller
Installation, Operation, and Maintenance Manual
(BAS-SVX20).
UC210
Binary
Outputs
Type
Output
Rating
Pilot duty
BO1 Fan 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO2 Spare Relay 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO3 Spare Relay 10A up to 277 Vac
10A at 30 Vac/VDC, 2A at
120 Vac, 8 A at 250 Vac
BO4 Fan ON/Off
24-27 Vac, 0.5A
Resistive VA
BO5 Heat stage 3 TRIAC
24-27 Vac, 0.5A
Resistive VA
BO6
Heat stage 2/Water
Valve Close TRIAC
24-27 Vac, 0.5A
Resistive VA
BO7
Heat stage 1/Water
Valve Open TRIAC
24-27 Vac, 0.5A
Resistive VA
BO8
Air Damper Close
TRIAC
24-27 Vac, 0.5A
Resistive VA
BO9
Air Damper Open
TRIAC
24-27 Vac, 0.5A
Resistive VA
Table 5. UC400 specifications
Storage
Temperature: -40 to 185°F (-40 to 85°C)
Humidity: 5% to 95% (non-condensing)
Operating
Temperature: -40 to 185°F (-40 to 85°C)
Humidity: 5% to 95% (non-condensing)
Input Voltage:
20.4-27.6 Vac, (24 Vac± 15% nominal), 50-60
Hz, 10.5 VA plus 1 VA per 20mA of 24 VDC load
plus 12 VA maximum per binary load