Installation
18 VAV-SVN09B-EN
All binary outputs from control board are 24 VAC.
Connection points for unit UCM controller are shown in
Control Diagrams:
Figure 44 and Figure 45 for the UCM 4.2
Figure 46 and Figure 47 for the VV550
Figure 48 and Figure 49 for the UC400
Figure 50 and Figure 51 for the UC210
The type of wire used would be a Plenum rated class 2
circuit cable (CL2P) or approved substitute.The wire can
be 18t o 22 gauge and be used at a distance of up to 100 ft.
VRRF DDC controller Power Wiring
In VRRF unit connect line voltage wires to optional
transformer or Connect 24VAC toTB1-1 (+) andTB1-2 (-)
Proper polarity must be maintained.TB1-1 is the hot side
(+) andTB1-2 is the ground side (-) of the 24VAC input.The
UCM cannot be powered from a common 24 VAC
transformer that is supplying power to a device containing
a full wave rectifier bridge in its power supply. The
acceptable voltage is 20 to 28 VAC (24 VAC cataloged).
However, voltages at either extreme may result in
increased system instability.
Communication Link Wiring
UC400 and UC210
Use 18 AWG Trane purple-shielded communication
wire for BACnet installations.
Link limit of 4,000 ft and 60 devices maximum (without
a repeater).
Use aTrane BACnet termination on each end of the
link.
Use daisy chain topology (See Figure 9).
Maintain polarity.
To ensure proper network communication, follow the
recommended wiring and best practices below when
installing communication wire:
All wiring must comply with the National Electrical
Code™ (NEC) and local codes.
Ensure that 24 Vac power supplies are consistent in
regards to grounding. Avoid sharing 24 Vac between
controllers.
Avoid over tightening cable ties and other forms of
cable wraps.This can damage the wires inside the
cable.
Do not run communication cable alongside or in the
same conduit as 24 Vac power.This includes the
conductors running fromTRIAC-type inputs.
In open plenums, avoid running wire near lighting
ballasts, especially those using 277 Vac.
Use same communication wire type, without
terminators, for the zone sensor communication stubs
from the UC400 controller IMC terminals to the zone
sensor communication module.
Zone Sensor communication wiring length limits of
300 ft. (100 m).
Note: For more details, refer to the Unit ControllerWiring
for theTracer SC™ System ControllerWiring Guide
(BAS-SVN03).
Pneumatic units:
Single Duct Electric Heat
Remove Power and Lock andTag out unit if it hasn't been
done already.
1. Disconnect PE switch(es) for each stage of heat from
electric heat control enclosure and replace them with
relay(s) from kit.
2. Connect line voltage wires to relay(s) Normally Open
contacts using existing wires that were connected to
PE switch(es) if possible. See
Figure 10, p. 19 or
Figure 11 , p. 20 for correct diagram connections
3. Control voltage will be field wired from relay coil(s) to
VRRF DDC controller binary output connections using
cable. See Control Diagrams:
a. Figure 44 and Figure 45 for the UCM 4.2
b. Figure 46 and Figure 47 for the VV550
c. Figure 48 and Figure 49 for the UC400
d. Figure 50 and Figure 51 for the UC210
Figure 9. BACnet MS/TP link wiring
BI LINK IMC
+
VDC
AI
AIAI AI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
BI LINK IMC
+
VDC
AI
AIAI AI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
BI LINK IMC
+
VDC
AI
AIAI AI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
+
+
BI LINK IMC
+
VDC
AI
AIAI AI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
+
BI LINK IMC
+
VDC
AI
AIAI AI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
+
Tracer SC
UC400
UC400
UC400
Zone
Sensor
Zone
Sensor
Zone
Sensor
Zone
Sensor
communications
jack wiring
Trane BACnet terminator
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Seitenansicht 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 55 56

Kommentare zu diesen Handbüchern

Keine Kommentare