Installation,Operation, and MaintenanceSeptember 2006 PTAC-SVX01C-ENPTEE070/PTHE070 (7,000 Btuh)PTEE090/PTHE 090 (9,000 Btuh)PTEE120/PTHE120 (12,000 B
10 PTAC-SVX01C-ENInstallationWARNINGLive Electrical Components!During installation, testing, servicing and troubleshooting of this product, it may be
PTAC-SVX01C-EN 11InstallationTable 3. Electric heat capacity and electrical data, models PTEE and PTHE(i)Nominal heating Building circuit requirement
12 PTAC-SVX01C-ENInstallationInstallation ProcedureWARNINGHazardous Voltage w/Capacitors!Disconnect all electric power, including remote disconnects b
PTAC-SVX01C-EN 13Installation2. Grasping the top and bottom flanges of the rear closure panel as shown in Figure 12, the entire panel is pulled out di
14 PTAC-SVX01C-ENInstallation1. All units required either a power cord or hard wire kit to power the unit2. The Hydronic chassis "W" ships w
PTAC-SVX01C-EN 15InstallationNote: If using a third party thermostat to control the unit, the thermostat must have a clearly marked OFF state or posit
16 PTAC-SVX01C-ENInstallationNotes: EN = Enabled - operations based on other logicNotes: N/C = No change from prior stateStep 8. Configure the display
PTAC-SVX01C-EN 17InstallationStep 9. Programmable SettingsThe controller has a total of six (7) parameters that are user-configurable:1. Vent Door Con
18 PTAC-SVX01C-ENInstallation1. Ventilation Door FunctionThe power door works based upon control logic functions. When the unit is on, the vent door w
PTAC-SVX01C-EN 19InstallationEnergy Management SystemOccupancy StatesThe controller is designed to handle two possible occupancy states:• occupied• oc
2 PTAC-SVX01C-ENTable of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Model Number Description . . . . . . . . . . . .
20 PTAC-SVX01C-ENInstallationTable 14. PTEE manual test sequenceStepIndoor Fan HighIndoor Fan LowRemote FanOutdoor FanCondensate Pump CompReversing V
PTAC-SVX01C-EN 21Sequence of OperationAutomatic 3-minute Compressor LockoutAfter the compressor cycles off, it will not restart for three minutes. Thi
22 PTAC-SVX01C-ENOperationNotes:1. Connection to R enables input functions W, Y, GL, GH, O,VT, and/or EN.2. Connect 24VAC, 3VA maximum Remote Fan Cont
PTAC-SVX01C-EN 23OperationNotes: Certified in accordance with the Unitary Air-Conditioner Equipment Certification Program, which is based on ARI Stand
24 PTAC-SVX01C-ENOperationNotes: Certified in accordance with the Unitary Air-Conditioner Equipment Certification Program, which is based on ARI Stand
PTAC-SVX01C-EN 25OperationTable 19. Cooling temperature change - air conditionersRoom air dry bulbRoom air wet bulbPTEE0701 PTEE0702 PTEE0901 PTEE090
26 PTAC-SVX01C-ENOperationNotes: Shaded area is rating ampere7570 12 16 13 16 11 15 10 1465 18 22 18 21 16 20 16 1960 24 28 23 26 21 25 21 2455 31 34
PTAC-SVX01C-EN 27OperationNotes: Shaded area is rating wattageTable 23. Heating total wattage input — heat pumpsOutside air dry-bulbRoom air dry-bulb
28 PTAC-SVX01C-ENOperationTable 25. Unit accessory model numbersDescription Part NumberArchitectural GrillesARCHITECTURAL ALUMINUM GRILLE BAYAAGL001A
PTAC-SVX01C-EN 29OperationTable 26. Hydronic heat optionsKit DescriptionHHydronicCoil TypeWWater CoilSSteam CoilAccessory TypeKKitPower Voltage01 208
PTAC-SVX01C-EN 3*All heat pump units must have electric heat.Digit 8—Main Power Supply1 = 230-208V/60Hz/1phase2 = 265V/60Hz/1phase4 = 115V/60Hz/1phase
30 PTAC-SVX01C-ENMaintenance ProceduresPerform the following maintenance procedures to ensure proper unit operation. WARNINGLive Electrical Components
PTAC-SVX01C-EN 31Maintenance5. Reinstall the filter by reattaching the hook to the bottom of the vent door and replacing the two screws, slide the cha
32 PTAC-SVX01C-ENMaintenanceLeak TestingRefrigerant leaks are best detected with a halide or electronic leak detector.WARNING Use of Pressure Regulato
PTAC-SVX01C-EN 33MaintenanceFigure 22. Refrigeration sealed system — heat pump (air conditioning modelFigure 23. Refrigeration sealed system — Heat pu
34 PTAC-SVX01C-ENMaintenance4. Start the vacuum pump and open the shut-off valve to the high vacuum gauge manifold only. After the compound gauge (low
PTAC-SVX01C-EN 35MaintenanceCooling Performance TestThermometersThe following precautions are necessary in observing the thermometer readings in the c
36 PTAC-SVX01C-ENMaintenance3. Locate the readings listed in the Operation section of this manual. You will note that these readings fall within the v
PTAC-SVX01C-EN 37MaintenanceResistance Test1. With no power, remove the leads from the compressor terminals.2. Touch the leads of an ohmmeter to termi
38 PTAC-SVX01C-ENMaintenanceTable 27. Thermistor indoor coil resistancex (C°)Rmin (kΩ)Rnom(kΩ)Rmax(kΩ)-40.0 327.6037 342.7771 358.6311-39.0 306.4713
PTAC-SVX01C-EN 39MaintenanceWARNINGHazardous Voltage!Disconnect all electric power, including remote disconnects before servicing. Follow proper locko
General Information© 2005 American Standard Inc. All rights reserved PTAC-SVX01C-ENNOTICE:Warnings and Cautions appear in appropriate sections through
40 PTAC-SVX01C-ENMaintenanceRemoving the Outdoor Coil and Outdoor Air Thermistors1. Remove the chassis from the wall.2. Remove the front cabinet.3. Re
PTAC-SVX01C-EN 41DiagnosticsThe controller is equipped to display a diagnostic code through the interface module; if the display is not present (Class
42 PTAC-SVX01C-ENTroubleshootingTable 31. Compressor output does not energizeProbable cause ExplanationRandom restart timer All controller outputs re
PTAC-SVX01C-EN 43TroubleshootingTable 34. Reversing valve output does not energizeRandom restart timer ExplanationPower up control wait All controlle
44 PTAC-SVX01C-ENTroubleshootingTable 37. Condensate pump does not energizeProbable cause ExplanationRandom restart timer All controller outputs rema
PTAC-SVX01C-EN 45Figure 29. 230/208V wiring diagram (07 models)GRYLORBKHILNLHNBRYLLOHINRDRDYLRDBK123456783.0KW123456788765432 12.0KW654321RDBKWHYL/GR1
46 PTAC-SVX01C-ENWiring DiagramFigure 30. 230/208V Wiring diagram (09, 12, 15 models)GRYLORBKHILNLHNBRYLLOHINRDRD YLRDBK876543215.0KW123456783.0KW1234
PTAC-SVX01C-EN 47Wiring DiagramFigure 31. 265V Wiring diagram (07 models)GRORYLORBKHILNLHNBRYLLOHINRDRDYLRDBK123456783.0KW123456788765432 12.0KW654321
48 PTAC-SVX01C-ENWiring DiagramFigure 32. 265V Wiring diagram (09, 12, 15)GRORYLORBKHILNLHNBRYLLOHINRDRD YLRDBK876543215.0KW123456783.0KW1234567887654
PTAC-SVX01C-EN 49Wiring DiagramFigure 33. Energy management systemFigure 34. 3rd party class 2 thermostat wiringFigure 35. Remote display wiringRWYGHG
PTAC-SVX01C-EN 5General InformationRefrigerant Handling ProceduresWARNINGContains Refrigerant!System contains oil and refrigerant under high pressure.
50 PTAC-SVX01C-ENFull 1st Year WarrantyTrane will repair or replace any part which proves to be defective due to workmanship or materials, free of cha
Literature Order Number PTAC-SVX01C-ENDate 09/06Supersedes PTAC-SVX01B-ENStocking Location Webb/MasonThe manufacturer has a policy of continuous produ
6 PTAC-SVX01C-ENPre-InstallationPre-Installation ConsiderationsBefore beginning installation, make the following considerations:1. Verify the wall op
PTAC-SVX01C-EN 7Pre-InstallationReceiving and HandlingShipping PackageThe chassis and the cabinet front ship in one carton. Accessories ship separate.
8 PTAC-SVX01C-ENUnit DimensionsFigure 4. Unit with wall sleeve and subbase accessoryFigure 5. Wall SleeveUnit Dimensions
PTAC-SVX01C-EN 9Unit DimensionsFigure 6. Top view of the hydronic kitFigure 7. Hydronic kit front viewFigure 8. Hydronic kit side viewPTAC Wall Sleeve