SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,
10 CLCH-SVN05A-ENAssembly and Installation3. Tighten nuts/bolts at all locations. Ensure lock nuts are securely tightened.4. Review the details curb
CLCH-SVN05A-EN 11Assembly and Installation5. Attach duct support members to each side of roof curb perimeter wall with self-drill screws. See Figure 1
12 CLCH-SVN05A-ENAssembly and Installation7. Install gasket along the perimeter of the pipe chase roof curb and unit roof curb. Gasketing is provided
CLCH-SVN05A-EN 13Assembly and InstallationPipe Cabinet Roof CurbsPipe cabinets ordered from Trane for field installation require special attention wit
14 CLCH-SVN05A-ENAssembly and InstallationFigure 17. Typical exploded view of curb with part numbers1385-011385-021384-011384-051384-031384-021384-04
CLCH-SVN05A-EN 15Assembly and InstallationTP1302-02 Outer Side Plate 9.88 x 5.00 1TP1302-03 Outer Side Plate 9.88 x 5.00 1TP1302-04 Outer Side Plate 9
16 CLCH-SVN05A-ENAssembly and InstallationSpecialty Roof CurbsUnits to be mounted on a roof curb not supplied by Trane require special attention. Cen
CLCH-SVN05A-EN 17Assembly and InstallationTable 4. Specialty roof curb dimensionsUnit Size Width Length3 30.50 Ls-14 43.00 Ls-16 43.00 Ls-18 49.50 Ls-
18 CLCH-SVN05A-ENAssembly and InstallationDuctwork RecommendationsSound AttenuationNoise is produced by unit supply fans, and exhaust fans. Supply fa
CLCH-SVN05A-EN 19Assembly and Installation• The first elbow in the ductwork leaving the unit should be no closer than 3 fan diameters from the unit, t
2 CLCH-SVN05A-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices.Note that warnings, cautions and notices appear at appropriate intervals
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, theleader in creating and sustaining safe, comf
CLCH-SVN05A-EN 3General InformationNameplateEach Performance air handler section shipped includes at least one nameplate/label (see Figure 1), which i
4 CLCH-SVN05A-ENGeneral InformationPreparing the Unit SiteEnsure the installation site can support the total weight of the air-handling unit, includi
CLCH-SVN05A-EN 5Installation ConsiderationsInstallation Considerations• Isolation rails should not be installed on top of Trane roof curbs. If isolati
6 CLCH-SVN05A-ENInstallation Considerations• If a unit is pier-mounted, at a minimum, locate one pier at each corner directly underneath any shipping
CLCH-SVN05A-EN 7Installation Considerations• Do not overlap counter flashing over the top of the roof curb. Counter flashing should extend to the bott
8 CLCH-SVN05A-ENAssembly and InstallationAssembly and InstallationThe following procedure explains how to assemble and install roof curbs provided by
CLCH-SVN05A-EN 9Assembly and Installation2. Attach outer and inner corner splice plates (4 places) (see Figure 11.Check curb dimensions for squareness