Specifications (3011)
Differential Pressure Range:
0 to 1.0 in. wg
Minimum Setpoint Range:
0 to 1.0" H
2
O
Maximum Setpoint Range:
minimum to 1.0 in. wg
Operating Static Range:
0.256.0 in. wg
Specifications (3011)
Normal Supply Air Pressure:
20.0 psi
Minimum Supply air Pressure:
15.0 psi
Maximum Supply Air Pressure:
30.0 psi
Average Supply Air Consumption:
28.8 scim at 20 psi
Thermostat Pressure Input Range:
Adjustable 0–10 psi band from 0–20 psi
Reset Start Point Range:
0–10 psi
Reset Span Range:
0–10 psi
Maximum Safe Thermostat Input:
30 psi (closed chamber)
Operating Temperature:
+40/+120°F
Storage Temperature:
-40/+140°F
Main, Thermostat, Actuator and Static
Pick-up Connections:
.250 O.D.