Trane CNT-SVX07C-EN Bedienungsanleitung Seite 41

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 84
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 40
Wiring requirements and options
CNT-SVX07C-EN 31
Figure 15. Two-pipe heating unit with face-and-bypass damper
LonTalk
in
Entering water
temperature
Outdoor air or
generic temperature
24 V
Exhaust (or fan, medium speed)
24 V
Fan, low speed
24 V
Fan, high speed
Low-coil-temperature detection
(closed=normal)*
Condensate overflow (closed=normal)*
Occupancy (open=occupied)*
LonTalk
H
N
24 Vac
24 V
Generic/baseboard heat
out
Fan status (closed=on)*
24 V
Outdoor air damper actuator
Discharge air
temperature
24 V
Face & bypass damper actuator
Open
Close
Close
Open
24 V
Heat isolation valve, open/close
* All binary inputs are configurable.
Connect 24 V to an AC POWER (24V) terminal.
AI4 input: See
Figures 5 and 6
on page 20 for
wiring options
Seitenansicht 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 83 84

Kommentare zu diesen Handbüchern

Keine Kommentare