Tubular Gas Fired Blower Style Unit HeaterNovember 2013GBNE-SVX001A-ENInstallation, Operationand MaintenanceSAFETY WARNINGOnly qualified personnel shou
10 GBNE-SVX001A-ENInstallation (continued)Gas PipingNOTICE: If more than one unit heater is to be served by the same piping arrangement, the total cu.
11GBNE-SVX001A-ENFigure 4 - Pipe Installation, Standard ControlsThe appliance and its individual shutoff valve must be disconnected from the gas suppl
12 GBNE-SVX001A-ENBLOWER DRIVE ADJUSTMENT1. Remove the belt guard and loosen the belt tension bolts on the blower motor base.2. Loosen the set scr
13GBNE-SVX001A-ENIVL442.8-3.8AK514.7Turns OpenIVL341.9-2.9AL646.0AL747.0AL848.0AK565.2AL10410.0MOTOR PULLEYS BLOWER PULLEYSPulley Table 1725 RPM Motor
14 GBNE-SVX001A-ENElectrical ConnectionsHAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to dis
15GBNE-SVX001A-ENElectrical Connections (continued)Figure 6d - Tubular Blower Units 100-150 with Single Stage Ignition, Natural Gas and Propane (LP) G
16 GBNE-SVX001A-ENElectrical Connections (continued)Figure 6e - Tubular Blower Units 100-150 with Two Stage Ignition, Natural Gas and Propane (LP) Gas
17GBNE-SVX001A-ENElectrical Connections (continued)Figure 6f - Tubular Blower Units 175-400 with Single Stage Ignition, Natural Gas and Propane (LP) G
18 GBNE-SVX001A-ENElectrical Connections (continued)Figure 6g - Tubular Blower Units 100-150 with Two Stage Ignition, Natural Gas and Propane (LP) Gas
19GBNE-SVX001A-ENVentingObserve the following precautions when venting the unit:1. Use flue pipe of the same size as the flue connections on the gas un
2 GBNE-SVX001A-ENTable of ContentsDescription ... 3Model Number Description ..
20 GBNE-SVX001A-ENHorizontal venting arrangements are designed to be used with single wall vent pipe. Horizontal venting arrangements must terminate e
21GBNE-SVX001A-ENADDITIONAL REQUIREMENT FOR CANADIAN INSTALLATIONSREFER TO SPECIFICATION TABLE AND INSTALLATION MANUAL FOR PROPER USAGE.* The followin
22 GBNE-SVX001A-ENVenting (continued)Figure 9BD3619CD3620FFigure 9A
23GBNE-SVX001A-ENFigure 10AFigure 10BVenting (continued)D3661FD3662D
24 GBNE-SVX001A-END6923BOperationPower Vented Blower Units Direct Spark IgnitionEXPLANATION OF CONTROLS:1. The unit heater is equipped with a power v
25GBNE-SVX001A-EN2. PROPANE GAS: An exact manifold pressure of 10.0 inches WC (2.5 kPa) must be maintained for proper operation of the unit heater. I
26 GBNE-SVX001A-ENTUBULAR UNIT HEATER HIGH ALTITUDE DERATIONThis Tubular Unit Heater has been manufactured utilizing standard burner orifices and a n
27GBNE-SVX001A-ENTable 9 - Tubular Propeller Troubleshooting GuideSYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTIONA. Flame pops back.1. Burner orifice too
28 GBNE-SVX001A-ENTable 9 - Tubular Propeller Troubleshooting Guide (continued)SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTIONL. Blower motor turns on an
29GBNE-SVX001A-ENNo Cycling or appliance power or thermostat call for heat since appliance failure has occurred.1. Check the system thermostat to make
3GBNE-SVX001A-ENNOTICE: It is the equipment owners responsibility to provide any scaffolding or other apparatus required to perform emergency service
30 GBNE-SVX001A-ENMaintenance2. Turn off the manual gas valve and electrical power to the unit heater.3. To clean or replace the burners, remove bur
31GBNE-SVX001A-ENLimited WarrantyPower Vented Tubular Blower Unit Heaters1. The "Manufacturer" warrants to the original owner at original i
32 GBNE-SVX001A-ENFigure 14 - Vestibule Panel/Tube Assembly Figure 15 - Electrical Control Panel AssemblyFigure 12 - Blower Parts Figure 13 - Componen
33GBNE-SVX001A-ENFigure 16 - Power Venter Assembly (100/250 Unit Sizes Shown)Figure 18 - Turbulator/High Limit LocationFigure 17 - Power Venter Assem
34 GBNE-SVX001A-ENCustomer ____________________________________ Job Name & Number _________________________PRE-INSPECTION INFORMATIONWith power
Trane optimizes the performance of homes and buildings around the world. A businessof Ingersoll Rand, the leader increating and sustaining safe, comfo
4 GBNE-SVX001A-ENDigit 1 - Gas Heating EquipmentG - Gas Heating EquipmentDigit 2 - Product TypeB - Tubular BlowerDigit 3 - Fuel TypeN - Natural GasP -
5GBNE-SVX001A-ENMake certain that the power source conforms to the electrical requirements of the heater.Special attention must be given to any ground
6 GBNE-SVX001A-ENTable 1 - Performance and Dimensional Data - Tubular Blower Unit Heater† Ratings shown are for unit installations at elevations betw
7GBNE-SVX001A-ENInstallationSince the unit is equipped with an automatic gas ignition system, the unit heater must be installed such that the gas igni
8 GBNE-SVX001A-ENInstallation (continued)Table 2 - Heat Throw DataStandard Heater 30° Nozzle 60° Nozzle 90° NozzleDegree of NozzleDistance From Floor
9GBNE-SVX001A-ENAIR FOR COMBUSTION: The unit heater shall be installed in a location in which the facilities for ventilation permit sati