Installation/OperationMaintenanceVariTrane™Pneumatic ControlsVAV-SVX02B-ENMarch 2002

Seite 2 - Thermostat

VAV-SVX02B-EN10Model 3501The model 3501 Pneumatic VolumeRegulator (PVR) is capable of operatingwith normally-open or normally-closedair valves and can

Seite 3

VAV-SVX02B-EN 11CalibrationProceduresCalibration Procedure (Steps 1–4 apply to all thermostat models)1. Be sure the PVR is installed correctly and tha

Seite 4 - Reversing Relay

VAV-SVX02B-EN12Specifications (3501)Differential Pressure Range:0 to 1.0 in. wgMinimum Setpoint Range:0 to 1.0" H2OMaximum Setpoint Range:minimum

Seite 5

VAV-SVX02B-EN 13MCP-3631—RotaryPneumatic Damper ActuatorDescription:Rotary actuators mounts to a standard½" diameter shaft by a locking collarand

Seite 6 - Model 3011—Pneumatic

VAV-SVX02B-EN14Constant Volume Dual-DuctCalibration (3011)This calibration procedure is used whena constant volume of air must bemaintained through a

Seite 7

VAV-SVX02B-EN 15Thermostat Range: 3–8 psiHeating Valve = 5 psi rangeThermostat Range: 8–13 psiCooling Valve = 5 psi rangeApproximately 1000 cfm divide

Seite 8

TraneAn American Standard Companywww.trane.comFor more information contactyour local district office ore-mail us at [email protected] Order

Seite 9 - Specifications (3011)

VAV-SVX02B-ENThermostat Selectionand LocationIn general, both one- and two-pipethermostats have a gain of 2.5 psi perdegree Fahrenheit, unless special

Seite 10 - Volume Regulator

3VAV-SVX02B-ENThermostatSpecificationsTP970 Series Pneumatic T-statsMaximum Safe Air Pressure:25psi (172 kPa)Maximum Safe Air Temperature:150°F (66°C)

Seite 11 - Procedures

VAV-SVX02B-ENInstallation and OperationThe reversing relay is a proportional,non-bleeding device for use in pneu-matic control systems where a propor-

Seite 12 - Specifications (3501)

5VAV-SVX02B-ENReversing RelayCalibrationBy using the “bias” adjustment on therelay, the factory-set 8.0–9.0 “cross-over” can be changed. To recalibrat

Seite 13 - Pneumatic Damper Actuator

VAV-SVX02B-ENModel 3011The model 3011 Pneumatic VolumeRegulator (PVR) is capable of operatingwith normally-open or normally-closedair valves and can o

Seite 14 - Calibration (3011)

7VAV-SVX02B-ENUse the following procedure to set-up the PVR:1. Select damper action (NO or NC). Loosen damper selection switch screw and align to eith

Seite 15 - Variable Air Volume Dual-Duct

VAV-SVX02B-ENCalibrationProceduresCalibration Procedure (Steps 1–4 apply to all thermostat models)1. Be sure the PVR is installed correctly and that a

Seite 16 - Single-Duct VAV (VCV 3011)

VAV-SVX02B-EN 9Specifications (3011)Differential Pressure Range:0 to 1.0 in. wgMinimum Setpoint Range:0 to 1.0" H2OMaximum Setpoint Range:minimum

Kommentare zu diesen Handbüchern

Keine Kommentare

Freecom Technologies IEEE 1394 Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Hardware Freecom Technologies IEEE 1394.
Wir stellen 1 PDF-Handbücher Freecom Technologies IEEE 1394 zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Bedienungsanleitung






Weitere Produkte und Handbücher für Hardware Freecom Technologies

Modelle Dokumententyp
XS 3.0 Bedienungsanleitung   Freecom Technologies XS 3.0 User Manual, 16 Seiten